RF IS M12 nb-ST 2 m
Wireless inductive sensor
Beskrivning
- Metal enclosure
- M12 x 1 thread
- Non-flush mounting
- To be connected to RF 96 ST or RF I/O universal transmitter
- With M12 coupling, 4-pole
Notes
- 2 mounting nuts are included in delivery
Technical data
Applied standards
EN 60947-5-2, EN 61000-6-2, EN 61000-6-3
Enclosure
brass, nickeled
Actuator
steel plate 12 x 12 x 1 mm, FE 360
Front cap
PVC, black
Back cap
PVC, black
Degree of protection
IP67 (IEC/EN 60529)
Connection
Coupling M12 x 1, 4-pole
Cable length
2 m
Ambient temperature
–25 °C … +70 °C
Rated insulation voltage Ui
75 VDC
Rated operating current Ie
0.2 mA
Rated operating voltage Ue
3 … 5 VDC
Rated switching distance sn
4 mm
Assured switching distance sa
0 … 3.24 mm
Real switching distance sr
3.6 … 4.4 mm
Hysteresis
approx. 10 %
Repeatability
≤ 5 %
Type of installation
non-flush
Switching frequency
see RF 96 ST / RF I/O
Correction factors
Steel (Fe360) = 1; Stainless steel approx. 0.7; Brass approx. 0.5; Aluminium approx. 0.4; Copper approx. 0.4
Note
The sensor may only be used in combination with RF 96 ST or RF I/O
Weight
98 g