LFH Fixed Fan Heater
Beskrivning
EXHEAT’s LFH Fixed Fan Heater combines superior efficiency with simple functionality to provide a next-generation heating solution for use in hazardous environments where the atmosphere is classified as Zone 1/2 (IIB+H2).
Certified to the new EN 80079-36 and EN 80079-37 standards for constructional safety, the LFH comes ready to ‘plug and play’, with the option of fitting a plug, or hard wiring to an isolator unit.
Incorporating a stainless steel casing for added toughness and durability, the LFH is designed to operate in ambient temperatures of -40°C to +40°C, and uses a framework allowing for multiple mounting options on floors, walls, and even ceilings.
- Stainless steel outer casing provides supreme protection, even in the harshest working environments
- Higher air flow allows for safe pressurising and heating of habitats for onsite repair works
- Various ducting options available upon request
- Bespoke protection device allows for operation in temperatures as low as -40°C
- Built in thermal protection monitor the heating elements to ensure temperature class is maintained
- Various mounting options for floors, walls and even ceilings available. Stackable mounting kit options available
- Suitable for Zone 1/2 (IIB+H2) hazardous areas
- Range also includes an even more high-powered range, the XLFH
- Can be supplied on a long flying lead to get heat where you need it
Downloads
Specifications
Certification | ATEX II 2 G D Ex db eb h IIB+H2 T2…T4 Gb Ex tb IIIC T300°C…T135°C Db IP65 IECEx CU TR(EAC) |
---|---|
Main Materials | Casing: Stainless steel Impeller: PA66 30% glass and steel filled blades and epoxy coated aluminium hub Element: Finned stainless steel tubular elements Ex e Enclosure: Stainless steel Ex d Enclosure: Anodised extruded aluminium |
Dimensions | LFH: Length 540mm, Width 600mm, Height 600mm. Base Weight 55kg XLFH: Length 690mm, Width 720mm, Height 680mm. Base Weight 75kg |
Mounting | Floor, wall, or ceiling mounting options available as standard. ANti-static castors available. |
Rating | Up to 40kW (depending on model) |
Temp Class | Available in T2, T3, and T4 temperature classes (depending on the model) |
Voltage | Three-phase: 380V to 690V, 50/60Hz |