ICG/653/UNIV | Ex d & Ex e Cable Gland

Integrated earthing ring suitable for single wire armour ‘W’, wire braid ‘X’ and tape armour ‘Z’.

 

Need help finding something? We're here to assist you. Call 031-84 03 00.

    Description

    The ICG/653/Universal cable gland is a Group II certified barrier cable gland suitable for installation in Zone 1/21 and Zone 2/22 hazardous areas. Double certified ATEX/IECEx (along with many others) for use in enhanced safety (Exe), flameproof (Exd), restricted breathing (ExnR) and dust (Ext) protection concepts. Integral earthing ring suitable for single wire armature ‘W’, wire braid ‘X’ and tape armature ‘Z’. Suitable for both elastomeric and plastic insulated cables, and especially for cables exhibiting cold flow characteristics on the inner sheath, are not effectively filled or contain hydroscopic fillers. The gland has a unique fully inspectable transparent elastomeric chamber The gland also provides an elastomeric seal on the inner sheath of the cable, and a low smoke, zero halogen IP seal on the outer sheath of the cable.

    Metallic body construction.

    • Fully inspectable chamber with elastomeric compound.
    • Available with either ExPress (liquid resin) or QSP (2-component hand-mixed compound), both with a cure time of 30 minutes.
    • Reversible reinforcement clamp – For all types of reinforcement and braids.
    • Patented cable entry tightening guide – Helps prevent damage caused by over-tightening.
    • Unique rear seal – Provides ultimate sealing over an extremely wide cable acceptance range.
    • Inspectable deluge seal – provides IP66, IP67, IP68 and IP69 ingress protection.
    • Available with metric or NPT threading.

    Teknisk data

    Applikation Farligt område Zon 1, Zon 21, Zon 2, Zon 22
    Skyddsklass
    • IP66, IP67, IP68 (30 metres for 7 days, special instruction apply)
    • IP69 to IEC/EN 60529
    • NEMA 4X
    • Deluge Protection to DTS01
    Material Mässing, Förnicklad mässing eller  316L Rostfritt stål
    Temperatur -60°C till +80 °C
    Serie Group II Hazardous Areas

    Certifikat och överensstämmelser

    ATEX File Number CML 18ATEX1268X, CML 19ATEX4507 (Ex nR)
    CSA File Number 1024328
    Certification
    • ATEX: CML 18ATEX1268X / CML 19ATEX4507 (Ex nR)
    • CCC: 2020312313000317
    • cCSAus: 1024328
    • DNV: TAE0000BS
    • EAC: No EA3C RU C-GB.HA91.B.00264/21
    • EQM: 20-11-27224/Q20-11-000979/NB0007
    • IECEx: CML 18.0131X / CML 21.0012X (Ex nR)
    • Inmetro: IEx 14.0272X
    • KCs: 17-KA4BO-0159X to 0167X
    • PESO: P450038
    • SONCAP: LCOGB049552-0500
    • UKEx: CML 21UKEX1132X / CML 21UKEX4133X (Ex nR)
    Hazardous Rating(s)
    • Ex II 2GD Ex db IIC Gb
    • Ex eb IIC Gb
    • Ex nR IIC Gc
    • Ex tb IIIC Db
    • Class I Div 1 ABCD
    • Class II Div 2 EFG and Class III
    • Class I, Zone I, AEx db IIC Gb
    • AEx eb IIC Gb
    • Zone 21, AEx tb IIIC Db
    IECEx File Number CML 18.0131X
    Industry Standard(s)
    • IEC/EN 62444 (Anchorage Type D)
    • IEC/EN 60079-0, 1, 7, 15, 31
    • CSA 60079-0, 1, 7, 31
    • CSA C22.2 No. 0-10, CSA C22.2 No. 174-18
    • UL2225
    • UL1203
    • UL 514B
    Ratings IK10 to IEC 62262

    Välj storlek för kabelförskruvningen

    Nedladdning

    Datablad Engelsk

    Cable Glands Part Code Logic

    Maintaining Ingress Protection

    Cable Glands Part Code Logic

     

    Hawke International