GMI PSD1220-098 Power Supply

SIL3 Power Supply PSD1220-098, 24Vdc, 20 A, Zone 2 / Div. 2 DIN Rail Mounting

 

    SKU: PSD1220-098 Categories: , Tag:

    Description

    The power supply type PSD1220-098 is an anodized aluminium unit. The power supply provides 24 Vdc, 20 A output. The PSD1220-098 unit can be connected in parallel with load-sharing circuitry, which distributes the current load equally to each power supply to increase reliability and reduce internal power loss. The power supply accepts AC power input sources with a nominal voltage range of 110 to 240 Vrms (±10%). Therefore, the lower limit is 100 Vrms, and the upper limit is 264 Vrms. The PSD1220-098 unit has the same AC, DC, Fault and Current Sharing connectors used in the PSD1210 power supply module for easy model-to-model switching.

    FUNCTIONS

    • SIL 3 for NE load according to IEC 61508:2010, with one PSD1220-098 module or more PSD1220-098 modules in redundant configuration (see ISM0371 for more information).
    • SIL 2 / SIL 3 for ND Load according to IEC 61508:2010, with two or more PSD1220-098 modules in redundant configuration (see ISM0371 for more information).
    • Systematic capability SIL 3.
    • Power factor correction.
    • Same AC, DC, Fault and Current Sharing connectors used in the PSD1210 power supply module for easy model-to-model switching.
    • Installation in Zone 2/Div. 2 hazardous locations.
    • EMC compatibility with EN61000-6-2, EN61000-6-4.
    • ATEX, IECEx, UL & C-UL, TÜV certifications.
    • TÜV functional safety certification.
    • Highly regulated output power of 24 Vdc, 20 A.
    • Over and under voltage alarm monitoring.
    • 3 overvoltage redundant protections.
    • Redundant parallel connections with load sharing.
    • Reduces power loss (in parallel/redundant configuration) by replacing a Schottky diode with Mosfet Active Ideal Diode.
    • Better than 93% efficiency @230 Vac input, full load and full output voltage range.
    • High load fuse breaking capability without interrupting operation.
    • Conformal coated on all boards for durability and protection.

    Technical data

    Supply

    AC Input voltage nominal 110 to 240 Vrms (±10 %), with frequency range 48 to 62 Hz.
    Power Factor Correction (AC input, full load) 0.97 typ.@230Vac, 0.995 typ.@115Vac
    Efficiency (full load, full Vout range) better than 93% @230Vac and 91% @115Vac.
    Efficiency (50% full load, full Vout range) better than 91% @230Vac, 90% @115Vac.
    Max. internal power dissipation (full load, 24 Vout) 35W @230Vac, 43W @115Vac.
    Max. internal power dissipation (50% full load) 24W @230Vac, 28W @115Vac.
    Max. AC input current (sinusoidal at full load) 4.8A @ 100Vac & full Vout range; 4.4A @ 110Vac & full Vout range; 2.2A (24Vout), 2.3A (25Vout), 2.4A (26Vout) @ 240Vac.
    Inrush current 15.7 Apeak @ 264Vac, 13 Apeak @ 230Vac, 5.2 Apeak @ 115Vac.
    AC connection plug-in screw connection terminal block suitable for 4mm2 wires.

    Isolation

    Input to Output isolation 2500 Vrms (routine test).
    Input to Ground isolation 1500 Vrms (routine test).
    Ground to Output isolation 500 Vrms (routine test).
    Output or Ground to Fault contact isolation 500 Vrms (routine test).

    Output

    Voltage 24 Vdc factory setting (adjustable range 23.6÷26.1 Vdc by front panel trimmer).
    Regulation 0.4% for a 100 % load change.
    Stability 0.03 % for a 20 % input line voltage change.
    Max. Ripple ≤ 300 mVpp.
    Output current 20 A (on full output voltage range and 230 Vac input). Parallel connection for redundancy with load sharing capability within ±2.5 % of output voltage setting.
    Output current limitation 22A @ 24Vout, 21A @ 25 & 26 Vout. Protected to short circuit.
    Output power up to 520 W @ 26 Vdc output and 230 Vac input.
    Max. Output Rise Time (after AC Input supplying) ≤ 2.4 sec.
    Dynamic Response 1.5 ms for 10-90% load change (overshoot ±2% of Vout setting).
    DC connection plug-in screw connection terminal block suitable for 4mm2 wires.
    Hold-up time at full load 20 msec (AC input).
    Overheat protection double overheat protection on the 1st and 2nd internal stages.
    Over voltage protection output limited to 28.5 Vdc plus two redundant crowbars for over voltage protection at 29 Vdc.

    Power good signaling

    Output good 22 V ≤ Vout ≤ 28 V
    Signaling voltage free SPST normally energized relay (contact closed), de-energize in over/under voltage conditions (contact open).
    Contact rating 2 A 50 Vac 100 VA, 2 A 24 Vdc 48 W (resistive load).
    Connection plug-in screw connection terminal block suitable for 2.5mm2 wires.

    Environmental conditions

    Operating temperature limits -40 to +60°C de-rated linearly 75-80% load above 50°C.
    Relative humidity limits 95%, up to 55°C
    Transport, storage temperature limits – 45 to + 85 °C.
    Max altitude 2000 m a.s.l.

    Mechanical

    Mounting EN/IEC60715 TH 35 DIN-Rail, into a cabinet.
    Weight 1.8 Kg (2 Kg with packaging).
    Location installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4.
    Protection class IP 20, Open Type.
    Dimensions Width 183 mm, Depth 124 mm, Height 124.5 mm

    Download

    Datasheet Engelsk

    Instructions manual PSD1220-098

    SaFTY manual PSD1220 and PSD1220-098

     

    G.M. International srl