GMI PSD1220-098 Power Supply
Description
The power supply type PSD1220-098 is an anodized aluminium unit. The power supply provides 24 Vdc, 20 A output. The PSD1220-098 unit can be connected in parallel with load-sharing circuitry, which distributes the current load equally to each power supply to increase reliability and reduce internal power loss. The power supply accepts AC power input sources with a nominal voltage range of 110 to 240 Vrms (±10%). Therefore, the lower limit is 100 Vrms, and the upper limit is 264 Vrms. The PSD1220-098 unit has the same AC, DC, Fault and Current Sharing connectors used in the PSD1210 power supply module for easy model-to-model switching.
FUNCTIONS
- SIL 3 for NE load according to IEC 61508:2010, with one PSD1220-098 module or more PSD1220-098 modules in redundant configuration (see ISM0371 for more information).
- SIL 2 / SIL 3 for ND Load according to IEC 61508:2010, with two or more PSD1220-098 modules in redundant configuration (see ISM0371 for more information).
- Systematic capability SIL 3.
- Power factor correction.
- Same AC, DC, Fault and Current Sharing connectors used in the PSD1210 power supply module for easy model-to-model switching.
- Installation in Zone 2/Div. 2 hazardous locations.
- EMC compatibility with EN61000-6-2, EN61000-6-4.
- ATEX, IECEx, UL & C-UL, TÜV certifications.
- TÜV functional safety certification.
- Highly regulated output power of 24 Vdc, 20 A.
- Over and under voltage alarm monitoring.
- 3 overvoltage redundant protections.
- Redundant parallel connections with load sharing.
- Reduces power loss (in parallel/redundant configuration) by replacing a Schottky diode with Mosfet Active Ideal Diode.
- Better than 93% efficiency @230 Vac input, full load and full output voltage range.
- High load fuse breaking capability without interrupting operation.
- Conformal coated on all boards for durability and protection.
Technical data
Supply |
|
AC Input voltage | nominal 110 to 240 Vrms (±10 %), with frequency range 48 to 62 Hz. |
Power Factor Correction (AC input, full load) | 0.97 typ.@230Vac, 0.995 typ.@115Vac |
Efficiency (full load, full Vout range) | better than 93% @230Vac and 91% @115Vac. |
Efficiency (50% full load, full Vout range) | better than 91% @230Vac, 90% @115Vac. |
Max. internal power dissipation (full load, 24 Vout) | 35W @230Vac, 43W @115Vac. |
Max. internal power dissipation (50% full load) | 24W @230Vac, 28W @115Vac. |
Max. AC input current (sinusoidal at full load) | 4.8A @ 100Vac & full Vout range; 4.4A @ 110Vac & full Vout range; 2.2A (24Vout), 2.3A (25Vout), 2.4A (26Vout) @ 240Vac. |
Inrush current | 15.7 Apeak @ 264Vac, 13 Apeak @ 230Vac, 5.2 Apeak @ 115Vac. |
AC connection | plug-in screw connection terminal block suitable for 4mm2 wires. |
Isolation |
|
Input to Output isolation | 2500 Vrms (routine test). |
Input to Ground isolation | 1500 Vrms (routine test). |
Ground to Output isolation | 500 Vrms (routine test). |
Output or Ground to Fault contact isolation | 500 Vrms (routine test). |
Output |
|
Voltage | 24 Vdc factory setting (adjustable range 23.6÷26.1 Vdc by front panel trimmer). |
Regulation | 0.4% for a 100 % load change. |
Stability | 0.03 % for a 20 % input line voltage change. |
Max. Ripple | ≤ 300 mVpp. |
Output current | 20 A (on full output voltage range and 230 Vac input). Parallel connection for redundancy with load sharing capability within ±2.5 % of output voltage setting. |
Output current limitation | 22A @ 24Vout, 21A @ 25 & 26 Vout. Protected to short circuit. |
Output power | up to 520 W @ 26 Vdc output and 230 Vac input. |
Max. Output Rise Time (after AC Input supplying) | ≤ 2.4 sec. |
Dynamic Response | 1.5 ms for 10-90% load change (overshoot ±2% of Vout setting). |
DC connection | plug-in screw connection terminal block suitable for 4mm2 wires. |
Hold-up time at full load | 20 msec (AC input). |
Overheat protection | double overheat protection on the 1st and 2nd internal stages. |
Over voltage protection | output limited to 28.5 Vdc plus two redundant crowbars for over voltage protection at 29 Vdc. |
Power good signaling |
|
Output good | 22 V ≤ Vout ≤ 28 V |
Signaling | voltage free SPST normally energized relay (contact closed), de-energize in over/under voltage conditions (contact open). |
Contact rating | 2 A 50 Vac 100 VA, 2 A 24 Vdc 48 W (resistive load). |
Connection | plug-in screw connection terminal block suitable for 2.5mm2 wires. |
Environmental conditions |
|
Operating temperature limits | -40 to +60°C de-rated linearly 75-80% load above 50°C. |
Relative humidity limits | 95%, up to 55°C |
Transport, storage temperature limits | – 45 to + 85 °C. |
Max altitude | 2000 m a.s.l. |
Mechanical |
|
Mounting | EN/IEC60715 TH 35 DIN-Rail, into a cabinet. |
Weight | 1.8 Kg (2 Kg with packaging). |
Location | installation in Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4 or Class I, Division 2, Group A,B,C,D, T4. |
Protection class | IP 20, Open Type. |
Dimensions | Width 183 mm, Depth 124 mm, Height 124.5 mm |