GMI PSD1001 Power Supply

SIL 3 – SIL 2 Quad ch. Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001

 

STATUS  >> PHASE-OUT
Next: SPARE-ONLY (2027-01-01)
ALTERNATIVE PRODUCT

Need help finding something? We're here to assist you. Call 031-84 03 00.

    SKU: PSD1001 Categories: , Tag:

    Description

    The PSD1001 is a quad channel DIN Rail Power Supply to drive measuring, process control equipments in Hazardous Area; it provides isolation between input and output. Typical application is to drive 4-20 mA 2 wires transmitter with local indication (current is not repeated in Safe Area). Output channels can be paralleled if more power is required.

    STATUS

    >> PHASE-OUT
    Next: SPARE-ONLY (2027-01-01)

    ALTERNATIVE PRODUCT

    Technical data

    Supply

    Voltage 24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
    Current consumption @ 24 V 110 mA with four channels at 20 mA nominal load, 140 mA with short circuit output.
    Power Dissipation 1.4 W with 24 V supply voltage and four channels at 20 mA nominal load.
    Max. power consumption at 30 V supply voltage and short circuit output, 3.8 W.

    Isolation

    Test Voltage I.S. Out/Supply 1.5 KV.

    Output

    Type 20 mA at 15 V per channel (20.5 V no load, 273 Ω series resistance).
    Short circuit current ≥ 24 mA per channel (26 mA typical).

    Environmental conditions

    Operating temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
    Storage temperature limits – 45 to + 80 °C.

    Safety description

    Safety parameters Uo/Voc = 23.6 V, Io/Isc = 88.2 mA, Po/Po = 519 mW at terminals 13-14, 15-16, 9-10, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.

    Mounting

    Type EN/IEC60715 TH 35 DIN-Rail.
    Weight about 120 g.
    Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
    Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
    Protection class IP 20.
    Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.

    Download

    Datasheet PSD1001  ENGLISH

    Instruction Manual PSD1001 ENGLISH 

    Instruction Manual D1001 ENGLISH