GMI D5254S Isolators
I.S. SIL2 2/4-Wire Transmitter Trip Amplifier
Description
The 2/4-Wire Transmitter Trip Amplifier D5254 provides a fully floating dc supply to energize conventional 2 wires 4-20 mA transmitters located in Hazardous Area; it also accepts 0/4-20 mA current input signals, as well as ±12 V voltage inputs from Hazardous Area. The module repeats/converts the input as on current signal, in a floating circuit to drive a Safe Area load, suitable for applications requiring SIL 2 in safety related systems for high risk industries. The output signal can be in direct or reverse form. Two independent Alarm Trip Amplifiers are also provided.
FEATURES
- SIL 2 / SC 3
- Input from Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- ±12 V Voltage Input
- 0/4-20 mA Active-Passive Input, Source-Sink Output
- Input and Output short circuit proof
- Modbus RTU RS-485 for monitor & configuration
- Out-of-range fault detection
- Optional alarm acknowledgement input
- Fully programmable operating parameters
- High Accuracy, μP controlled A/D converter
- Three port isolation, Input/Output/Supply
Technical data
Supply |
|
Type | 24 Vdc nom (21.5 to 30 Vdc), reverse polarity protected. |
Current Consumption | 110 mA @ 24 Vdc with 20 mA input/output and alarm relays energized, typical. |
Power Dissipation | 2.3 W @ 24 Vdc with 20 mA input/output and alarm relays energized, typical. |
Input |
|
Type | 0/4 to 20 mA (separately powered input, voltage drop ≤ 0.5 V) or 4 to 20 mA (2 wires Tx current limited ≈ 25 mA), or voltage input ±12 V. |
Integration time | 100 ms. |
Input range | 0 / +25 mA for current, ± 12 V for voltage. |
Transmitter line voltage | 15.5 V typical, 15.0 V minimum, @ 20 mA. |
Acknowledgement input |
|
Type | Logic level reverse polarity protected. |
Voltage range | 0 V ≤ OFF ≤ 5 V, 18 V ≤ ON ≤ 30 V. |
Current Consumption | 10 mA @ 24 Vdc, typical. |
Output |
|
Type | Fully customizable 0/4 to 20 mA, on max. 300 Ω load source mode, current limited @ 25 mA. |
Transfer characteristic | linear, direct or reverse, square root. |
Response time | ≤ 100 ms (10 to 90% step change). |
Alarm |
|
Trip point range | within rated limits of input sensor. |
Output | two voltage free SPDT relay contacts. |
Contact rating | 4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W (resistive load). |
DC and AC load breaking capacity | refer to Instruction Manual. |
Modbus interface |
|
Type | Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control. |
Isolation |
|
Test Voltage | I.S. In/Other 1.5 kV; Alarms/Other 1.5 kV; Alarm/Alarm 1.5 kV; Out/Supply 500 V; Out/Ack 500 V; Ack/Supply 500 V. |
Environmental conditions |
|
Operating temperature | temperature limits –40 to +70 °C. |
Storage temperature | temperature limits -45 to +80 °C. |
Safety description |
|
Equipment | Associated apparatus and non-sparking electrical equipment. |
Safety parameters | Uo = 26 V, Io = 91 mA, Po = 588 mW at terminals 13-14 Uo = 1.1 V, Io = 56 mA, Po = 16 mW at terminals 14-16 Uo = 1.1 V, Io = 0.012 mA, Po = 0.004 mW at terminals 15-16 Ui = 30 V at terminals 14-16 or 15-16, Ii = 128 mA at terminals 14-16, Ci = 2.1 nF, Li = 0 nH at terminals 13-14-15-16. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
Mounting |
|
Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
Weight | about 120 g. |
Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 22.5 mm, Depth 123 mm, Height 120 mm. |
Download
Datablad Engelsk
Instruktionsmanual, 5254S
Instruktionsmanual, D5000 – D5200 Series