GMI D5094S Safty Relay
Description
The D5094 is a relay module suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input and output contacts. It makes available 2+2 NO relay contacts connected in parallel and then in series to avoid spurious trip and to increase process availability. High process availability SIL 3 Safety Function for both Normally Energized (NE) and Normally De-energized (ND) / F&G loads is available. Load can be isolated from supply on both polarities. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering.
FEATURES
- SIL 3 / SC 3 for NE/ND loads with NE/ND driver
- Installation in Zone 2
- Up to 5 A functional / 6 A inrush current
- Load disconnection on both supply lines available
- High process availability to avoid spurious trips
- Compatible with DCS/PLC pulse testing
- Service contact available
- Input/Output isolation
CHANNELS
Technical data
Input |
|
Type | 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
Current Consumption | 45 mA @ 24 Vdc, typical. |
Power Dissipation | 1.1 W @ 24 Vdc, typical. |
Output |
|
Type | Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 7-11 and 8-12, close when relay energized, open in de-energized condition. |
Contact material | Ag Alloy (Cd free), gold plated. |
Contact rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
Contact min. switching current | 1 mA. |
Contact inrush current | 6 A @ 24 Vdc, 250 Vac. |
DC and AC load breaking capacity | refer to Instruction Manual. |
Mechanical / electrical life | 5 * 10⁶ / 3 * 10⁴ operation, typical. |
Operate / release time | 30 ms / 30 ms, typical. |
Isolation |
|
Test Voltage | Output/Input 2.5 kV. |
Environmental conditions |
|
Operating temperature | temperature limits –40 to +70 °C. |
Storage temperature | temperature limits -45 to +80 °C. |
Mounting |
|
Type | DIN-Rail 35 mm, or on custom Term. Board. |
Weight | about 125 g. |
Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
Download
Datasheet Engelsk
Instruction manual D5090S
Instruction manual D5000 – D5200 SERIES
G.M. International srl