GMI D5072D Intrinsically Safe Isolators
I.S. SIL2 Multifunction Temperature Converter
Description
The Multifunction Temperature Converter D5072 accepts a low level dc signal from millivolt, thermocouple or 2-3-4 wire resistance/RTD or transmitting potentiometer sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load, suitable for applications requiring SIL 2 level in safety related systems for high risk industries. Output signal can be direct or reverse. Modbus RTU RS-485 output is available on Bus connector. Cold junction compensation can be programmed as Internal: provided by an internal temperature sensor; Fixed: to a user-customizable temperature value; Remote: (only D5072D) connecting compensation RTD to one of the two ch. For D5072D module: duplicator function provides two independent outputs from one single input. Output function can be configured as: Adder, subtractor, low/high selector. Modules are provided with alarm function, which is available via photoMOS output.
FEATURES
- SIL 2 / SC 3
- Input from Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- mV, TC, 2/3/4wire res./RTD or potentiometer input
- Duplication/inversion/scaling/custom output
- Selectable CJC: internal PT1000, external RTD or fixed
- Fastest integration time: 50 ms
- Burnout/internal/cjc/in sensor fault monitor
- Alarm output with user-settable trip points
- Modbus RTU RS-485 for monitor & configuration
- Fully programmable operating parameters
- High Accuracy, µP controlled A/D converter
- Three port isolation, Input/Output/Supply
- High Density, two channels per unit
CHANNELS
Technical data
Supply |
|
Voltage | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected |
Current Consumption | 50 mA @ 24 Vdc with 20 mA out, typical. |
Power Dissipation | 1.0 W @ 24 Vdc with 20 mA out, typical. |
Input |
|
Type | Millivolt, thermocouple, 2-3-4 wire RTD or 3 wire transmitting potentiometer. Refer to Instruction Manual for more details. |
Integration time | from 50 ms to 500 ms. |
Input range | ±500 mV (TC/mV), 0-4 kΩ (RTD/res), up to 10 kΩ (pot). |
Thermocouple reference junction compensation | programmable: internal Pt1000, fixed, external, or remote. |
Output |
|
Type | Fully customizable 0/4 to 20 mA, on max. 300 Ω load source mode, current limited @ 24 mA. Refer to Instruction Manual for more details. |
Transfer characteristic | linear, direct or reverse on all input sensors. |
Modbus interface |
|
Type | Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control. |
Input performance |
|
Ref. Conditions | 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD. |
Calibration and linearity accuracy | refer to Instruction Manual. |
Temp. influence | refer to Instruction Manual. |
Ref. junction compensation accuracy | ≤ ± 1 °C. |
Output performance |
|
Ref. Conditions | 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature, slow integration mode, 3/4 wires configuration for RTD. |
Calibration accuracy | ≤ ± 10 µA |
Linearity error | ≤ ± 10 µA. |
Temp. influence | ≤ ± 2 µA/°C |
Isolation |
|
Test Voltage | I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. |
Environmental conditions |
|
Operating temperature | temperature limits –40 to +70 ° |
Storage temperature | temperature limits –45 to +80 °C. |
Safety description |
|
Equipment | Associated apparatus and non-sparking electrical equipment. |
Safety parameters | Uo = 7.2 V, Io = 16 mA, Po = 27 mW, Ui = 12.8 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9, 10-11-12. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
Mounting |
|
Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
Weight | about 135 g |
Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
Download
Datasheet Engelsk
Instructions manual, 5072
Instruction manual, D5000 – D5200 Series