GMI D5062S Isolators

I.S. SIL2 Vibration Transducer Interface

Need help finding something? We're here to assist you. Call 031-84 03 00.

    SKU: D5062S Categories: , Tags: ,

    Description

    The Vibration Transducer Interface D5062S is a high integrity analog input interface suitable for applications requiring SIL 2 level in safety related systems for high risk industries. It provides a fully floating dc supply for energizing vibration transducers, accelerometers or 2-3 wires sensors located in Hazardous Area, and repeats the sensor input voltage in a totally isolated circuit located in Safe Area to drive vibration monitors or analyzers for rotating machinery control and supervision purposes.

    FEATURES

    • SIL 2 / SC 3
    • Input from Zone 0/Div. 1
    • Installation in Zone 2/Div. 2
    • 0 to –20 V Input/Output Signal
    • Wide band signal transfer
    • Input and Output short circuit proof
    • In-field programmability by DIP Switch
    • High Accuracy
    • Three port isolation, Input/Output/Supply

    Teknisk data

    Supply

    Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
    Current Consumption 90 mA @ 24 Vdc with 20 mA transducer consumption and 2 mA output load, typical.
    Power Dissipation 2.0 W @ 24 Vdc with 20 mA transducer consumption and 2 mA output load, typical.

    Input

    Type 0 V to -20 V (10 kΩ impedance at terminals 7-8 or 8-9).
    3 wires sensor supply voltage more than -22 V @ 0 mA supply, more than -17 V @ 15 mA supply (current limited @ ≈ 23 mA).
    2 wires sensor supply voltage more than -17 V with constant current supply.
    2 wires sensor supply current selectable @ 4 mA, 6 mA or 10 mA via internal DIP–Switch.

    Output

    Type 0 to -20 V on 10 kΩ load, with 10 Ω output resistance.
    Response time ≤ 10 µs (10 to 90 % step change).
    Frequency response DC to 20 kHz within 1 dB maximum.

    Performance

    Ref. Conditions 24 V supply, 10 kΩ load, 23 ± 1 °C ambient temperature
    Calibration accuracy ≤ ± 0.1 % FSR
    Linearity accuracy ≤ ± 0.05 % FSR
    Temp. influence ≤ ± 0.005 % on zero/span for a 1 °C change.

    Isolation

    Test Voltage I.S. In/Out 1.5 kV; I.S. In/Supply 1.5 kV; Out/Supply 500 V

    Environmental conditions

    Operating temperature temperature limits –40 to +70 °C
    Storage temperature temperature limits –45 to +80 °C

    Safety description

    Equipment Associated apparatus and non-sparking electrical equipment
    Safety parameters Uo = 27 V, Io = 90 mA, Po = 576 mW at terminals 7-8-9-10. Ui = 30 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

    Mounting

    Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
    Weight about 125 g.
    Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG).
    Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

    Nedladdning

    Datasheet Engelsk

    Instructions manual, 5254S

    Instruction manual, D5062S Series

     

    G.M. International srl