The Repeater Power Supply D5014 module is a high integrity analog input interface suitable for applications requiring SIL 3 level in safety related systems for high risk industries. It provides a fully floating dc supply for energizing conventional 2 wires 4-20 mA, active or passive, transmitters located in Hazardous Area, and repeats the current in floating circuit to drive a Safe Area load. The module supports output current duplication and it allows bi-directional communication signals, for HART® devices.
FEATURES
- SIL 3 / SC 3
- Input from Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- 2 fully independent channels
- 4-20 mA Active-Passive Input, Source-Sink Output
- Output current duplication available
- HART® compatible
- Input and Output short circuit proof
- In-field programmability by DIP Switch
- High Accuracy
- Three port isolation, Input/Output/Supply
- High Density, two channels per unit
CHANNELS
Technical data
Supply |
|
Voltage | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected |
Current Consumption | 90 mA @ 24 Vdc with 20 mA out, typical. |
Power Dissipation | 1.35 W @ 24 Vdc with 20 mA out, typical. |
Input |
|
Type | 4 to 20 mA (separately powered input, voltage drop ≤ 0.5 V) or 4 to 20 mA (2 wires Tx current limited ≈ 25 mA), reading range 0 to 24 mA. |
Transmitter line voltage | 15.0 V typical, 14.5 V minimum, @ 20 mA. |
Output |
|
Type | 4 to 20 mA, on max. 550 Ω load in source mode (typical 12 V compliance); V min. 8 V @ 0 Ω load V max. 30 V in sink mode, current limited ≈ 25 mA or 1 to 5 V on internal 250 Ω shunt. Output current duplication available (D5014D). |
Response time | 5 ms (0 to 100 % step change). |
Performance |
|
Ref. Conditions | 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
Calibration accuracy | ≤ ± 0.1 % FSR. |
Linearity accuracy | ≤ ± 0.05 % FSR. |
Temp. influence | ≤ ± 0.01 % FSR on zero/span for a 1 °C change. |
Isolation |
|
Test Voltage | I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. |
Environmental conditions |
|
Operating temperature | temperature limits –40 to +70 °C. |
Storage temperature | temperature limits –45 to +80 °C. |
Safety description |
|
Equipment | Associated apparatus and non-sparking electrical equipment. |
Safety parameters | Uo = 25.9 V, Io = 92 mA, Po = 594 mW at terminals 7-8, 9-10. Uo = 1.1 V, Io = 56 mA, Po = 16 mW at terminals 8-11, 10-12. Ui = 30 V, Ii = 128 mA, Ci = 0 nF, Li = 0 nH at terminals 8-11, 10-12. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
Mounting |
|
Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
Weight | about 155 g |
Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |