Ex ZS 92 S 22 VD F

 

Ex emergency pull-wire switch

    Description

    • Ex zone 1 and 21
    • Corrosion-resistant aluminium enclosure
    • Screws made of stainless steel
    • Wire length up to 2 x 100 m
    • Release by lever
    • F = Reset lever at the front side
    • Back and base mounting possible
    • Wire pull and breakage detection

    Notes

    • At 3 m distance intermediate wire supports are required. Two compensation springs type ZS 90/91/92 S must be installed, see accessories.

    Technical data

    Applied standards

    EN 60947-5-1, EN 60947-5-5, EN ISO 13850, EN ISO 13849-1, EN IEC 60079-0, EN 60079-1, EN IEC 60079-7, EN 60079-31, EN 620-5.7.2.9, AS 1755-2000-2.7.9.1, AS/NZS 4024.3610:2015-2.10.6.2

    Enclosure

    aluminium die-cast, corrosion-resistant, powder-coated, passivated, shockproof, anthracite grey, similar to RAL 7016

    Cover

    aluminium die-cast, corrosion-resistant, powder-coated, passivated, shockproof, signal yellow, similar to RAL 1003

    Actuating lever

    aluminium die-cast, corrosion-resistant, powder-coated, passivated, shockproof, signal red, similar to RAL 3001

    Reset lever

    aluminium die-cast, corrosion-resistant, powder-coated, passivated, shockproof, sky blue, similar to RAL 5015

    Screws

    stainless steel

    Tightening torque

    cover screws: max. 2.5 Nm
    actuator screws: max. 6 Nm

    Degree of protection

    IP65 (EN 60079-0 + IEC/EN 60529)

    B10d (10 % load)

    100 000

    TM

    max. 20 years

    Contact material

    silver

    Switching system

    snap action, positive break NC contacts A

    Switching elements

    2 NC/2 NO contacts, type Zb

    Connection

    screw connection terminals

    Cable cross-section

    min. 0.75 mm² (AWG 18), max. 2.5 mm² (AWG 14), incl. conductor ferrules

    Cable entry

    2 x M25 x 1.5

    Rated impulse withstand voltage Uimp

    6 kV

    Rated insulation voltage Ui

    250 V

    Conventional thermal current Ithe

    2 A / 4 A / 6 A

    Utilisation category

    AC-15

    Rated operating current/voltage Ie/Ue

    max. 2 A/4 A/6 A / 250 VAC

    Short-circuit protection

    2 A / 4 A / 6 A gG/gN fuse

    Mechanical life

    > 50 000 operations

    Max. wire length

    2 x 100 m

    Ambient temperature

    –10 °C … +55 °C max. 2 A,
    –10 °C … +50 °C max. 4 A,
    –10 °C … +45 °C max. 6 A

    Degree of pollution

    3

    Actuating force

    actuating lever approx. 30 N; reset lever approx. 40 N

    Ex marking

    L II 2G Ex db eb IIC T6 Gb,
    L II 2D Ex tb IIIC T80 °C Db
    IECEx Ex db eb IIC T6 Gb,
    Ex tb IIIC T80 °C Db

    Approvals

    BVS 19 ATEX E 076
    IECEx BVS 19.0074
    f d a

    Weight

    1900 g

    Download

    Mounting and wiring instructions – Ex ZS 92 S

    German, English, French, Italian, Portuguese, Russian

    Data sheet – Ex ZS 92 S 22 VD F

    English

    .steute