501/453/UNIV | Ex d & Ex e cable gland

 

This cable gland is the first and only cable gland that can be upgraded to a barrier solution in the field. Read more in the datasheet.

    Description

    The cable gland 501/453/Universal is double certified ATEX/IECEx (along with many others) for use in increased safety (Exe), flame retardant (Exd), restricted breathing (ExnR) and dust (Ext) protection concepts. Integrated earthing ring suitable for single wire armature ‘W’, wire braid ‘X’ and tape armature ‘Z’. Suitable for both elastomeric and plastic insulated cables, and especially for cables exhibiting cold flow characteristics on the inner sheath. The gland also provides an elastomeric seal on the inner sheath of the cable, and a low smoke, zero halogen IP seal on the outer sheath of the cable.

    Elastomeric Exd passive membrane seal on the cable inner jacket – helps eliminate cold flow and is fully inspectable on site.
    Reversible reinforcement clamp – for all types of reinforcement, braid and tape.
    Patented cable entry tightening guide – Helps prevent damage caused by over-tightening.
    Unique rear seal – provides ultimate sealing over an extremely wide cable acceptance range.
    Inspectable deluge seal – provides IP66, IP67, IP68 and IP69 ingress protection.
    Available with metric or NPT threading.

    This cable gland is the first and only cable gland that can be upgraded to a barrier solution in the field, read more in the datasheet.

    Technical data

    Applikation Farligt område Zon 1, Zon 21, Zon 2, Zon 22
    Skyddsklass
    • IP66, IP67 IP68 (30 metres for 7 days, special conditions may apply) and IP69 to IEC/EN 60529
    • NEMA 4X
    • Deluge Protection to DTS01
    Material Mässing, Förnicklad mässing eller  316L Rostfritt stål
    Arbetstemperatur -60°C to +80 °C
    Serie Group II Hazardous Areas

    Certifikat och överensstämmelser

    ATEX CML 18ATEX1268X, CML 19ATEX4507 (Ex nR)
    CSA 1015065
    Certifikat
    • ATEX: CML 18ATEX1268X / CML 19ATEX4507 (Ex nR)
    • CCC: 2020312313000318
    • cCSAus: 1015065
    • DNV: TAE0000BS
    • EAC: No EA3C RU C-GB.HA91.B.00264/21
    • EQM: 20-11-27224/Q20-11-000979/NB0007
    • IECEx: CML 18.0131X / CML 21.0012X (Ex nR)
    • Inmetro: IEx 14.0272X
    • KCs: 17-KA4BO-0631X to 0633X
    • PESO: P450038
    • SONCAP: LCOGB049552-0500
    • UKEx: CML 21UKEX1132X / CML 21UKEX4133X (Ex nR)
    Hazardous Rating(s)
    • Ex II 2GD Ex db eb IIC Gb
    • Ex nR IIC Gc
    • Ex tb IIIC Db
    • Class I, Zone I, AEx eb IIC Gb
    • Zone 21, AEx tb IIIC Db
    • Class I Div 2 ABCD
    • Class II Div 2 EFG
    • Class III
    IECEx File Number IECEx CML 18.0131X
    Industri Standard(s)
    • IEC/EN 62444 (Anchorage Type D)
    • IEC/EN 60079-0, 1, 7, 15, 31
    • CSA 60079-0, 1, 7, 31
    • CSA C22.2 No. 0-10, CSA C22.2 No. 174-18
    • UL 60079-0, 7, 31
    • UL2225
    • UL1203
    • UL514B
    Ratings IK10 to IEC 62262

    Choose size for cable gland

    Downloads

    Datablad Engelsk

    Maintaining Ingress Protection

    AI2000 – 501 453 UNIV Assembly Instructions

    AI2037 | Barrier Upgrade Kit

    Cable Glands Part Code Logic

     

    Hawke international