GMI PSD1001 Power Supply
SIL 3 – SIL 2 Quad ch. Power Supply for Hazardous Area Equipment DIN-Rail Model PSD1001
Description
The PSD1001 is a quad channel DIN Rail Power Supply to drive measuring, process control equipments in Hazardous Area; it provides isolation between input and output. Typical application is to drive 4-20 mA 2 wires transmitter with local indication (current is not repeated in Safe Area). Output channels can be paralleled if more power is required.
STATUS
ALTERNATIVE PRODUCT
Technical data
Supply |
|
Voltage | 24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Current consumption @ 24 V | 110 mA with four channels at 20 mA nominal load, 140 mA with short circuit output. |
Power Dissipation | 1.4 W with 24 V supply voltage and four channels at 20 mA nominal load. |
Max. power consumption | at 30 V supply voltage and short circuit output, 3.8 W. |
Isolation |
|
Test Voltage | I.S. Out/Supply 1.5 KV. |
Output |
|
Type | 20 mA at 15 V per channel (20.5 V no load, 273 Ω series resistance). |
Short circuit current | ≥ 24 mA per channel (26 mA typical). |
Environmental conditions |
|
Operating | temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
Storage | temperature limits – 45 to + 80 °C. |
Safety description |
|
Safety parameters | Uo/Voc = 23.6 V, Io/Isc = 88.2 mA, Po/Po = 519 mW at terminals 13-14, 15-16, 9-10, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting |
|
Type | EN/IEC60715 TH 35 DIN-Rail. |
Weight | about 120 g. |
Connection | by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Protection class | IP 20. |
Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |