501/421 | Ex d & Ex e | Cable Gland

The Hawke 501/421 is a Group II certified single seal cable gland suitable for installation in Zone 1/21 and Zone 2/22 hazardous areas.

.

    Description

    The Hawke 501/421 is a Group II certified single seal cable gland suitable for installation in Zone 1/21 and Zone 2/22 hazardous areas. Dual Certified ATEX/IECEx (along with many more) for use in Increased Safety (Exe), Flameproof (Exd), Restricted Breathing (ExnR) and Dust (Ext) protection concepts. For use with non-armoured elastomer and plastic insulated cables. This cable gland may be used with braided cables where the braid and outer sheath pass into the enclosure, and the requirements of 60079-14 are met.

    • Single elastomeric compression Exd seal on cable outer sheath
    • Rounded cable entry to prevent cable damage
    • Available with metric or NPT entry threadforms

    Teknisk data

    Applikation Farligt område Zon 1, Zon 21, Zon 2, Zon 22
    Skyddsklass
    • IP66, IP67 IP68 (30 metres for 7 days, special conditions may apply) and IP69 to IEC/EN 60529
    • NEMA 4X
    • Deluge Protection to DTS01
    Material Mässing, Förnicklad mässing eller  316L Rostfritt stål
    Temperatur -60°C till +100 °C
    Serie Group II Hazardous Areas

    Certifikat och överensstämmelser

    ATEX File Number CML 19ATEX1167X
    CML 19.0045X
    CSA File Number CSA1015065
    Certification
    • ATEX: CML 19ATEX1167X / CML 19ATEX4507X (Ex nR)
    • CCC: 2020312313000315
    • cCSAus: 1015065
    • DNV: TAE0000BS
    • EAC: No EA3C RU C-GB.HA91.B.00264/21
    • EQM: 20-11-27224/Q20-11-000979/NB0007
    • IECEx: CML 19.0045X / CML 21.0012X (Ex nR)
    • Inmetro: IEx 14.0272X
    • KCs: 17-KA4BO-0634X to 0637X
    • PESO: P450038
    • SONCAP: LCOGB049552-0500
    • UKEx: CML 21UKEX1161X / CML 21UKEX4133X (Ex nR)
    Hazardous Rating(s)
    • Ex II 2GD Ex db eb IIC Gb
    • Ex nR IIC Gc
    • Ex tb IIIC Db
    • Class I, Zone I, AEx eb IIC Gb
    • Zone 21, AEx tb IIIC Db
    • Class I, Div.2 Groups ABCD
    • Class II Div.2, Groups EFG
    • Class III
    Industry Standard(s)
    • IEC/EN 62444 (Anchorage Type B)
    • IEC/EC 60079-0, 1, 7, 15, 31
    • CSA 60079-0, 1, 7, 31
    • UL 60079-0, 7, 31
    • UL514B
    • UL1203
    • UL2225
    Ratings IK10 to IEC 62262

     

    Certifications And Compliance

    ATEX File Number
    CML 19ATEX1167X
    CML 19.0045X
    Certification
    • ATEX: CML 19ATEX1167X / CML 19ATEX4507X (Ex nR)
    • CCC: 2020312313000315
    • cCSAus: 1015065
    • DNV: TAE0000BS
    • EAC: No EA3C RU C-GB.HA91.B.00264/21
    • EQM: 20-11-27224/Q20-11-000979/NB0007
    • IECEx: CML 19.0045X / CML 21.0012X (Ex nR)
    • Inmetro: IEx 14.0272X
    • KCs: 17-KA4BO-0634X to 0637X
    • PESO: P450038
    • SONCAP: LCOGB049552-0500
    • UKEx: CML 21UKEX1161X / CML 21UKEX4133X (Ex nR)
    CSA File Number
    CSA1015065
    Hazardous Rating(s)
    • Ex II 2GD Ex db eb IIC Gb
    • Ex nR IIC Gc
    • Ex tb IIIC Db
    • Class I, Zone I, AEx eb IIC Gb
    • Zone 21, AEx tb IIIC Db
    • Class I, Div.2 Groups ABCD
    • Class II Div.2, Groups EFG
    • Class III
    Industry Standard(s)
    • IEC/EN 62444 (Anchorage Type B)
    • IEC/EC 60079-0, 1, 7, 15, 31
    • CSA 60079-0, 1, 7, 31
    • UL 60079-0, 7, 31
    • UL514B
    • UL1203
    • UL2225
    Ratings
    IK10 to IEC 62262

    Välj storlek för kabelförskruvningen

    Nedladdning

    Datablad Englesk

    Cable Glands Part Code Logic

    Maintaining Ingress Protection

    AI307 | 501/421 Installation Instruction

    Cable Glands Part Code Logic

     

    Hawke International