GMI D5020D Isolators

I.S. SIL2 HART® Isolating Driver

    SKU: D5020D, D5020 Categories: , Tags: ,

    Description

    The Isolating Driver D5020 module is a high integrity analog output interface suitable for applications requiring SIL 2 level in safety related systems for high risk industries. It isolates and transfers a 4- 20 mA signal from a controller located in Safe Area to a load in Hazardous Area. It has a high output capacity combined with a low drop across its input terminals. The circuit allows bi-directional communication signals, for HART® smart positioners. Line and load open/short circuit detection is provided: the fault in the field is directly mirrored to the PLC AO and it is also reported by opening the fault output.

    FEATURES

    • SIL 2 / SC 3
    • Output to Zone 0/Div. 1
    • Installation in Zone 2/Div. 2
    • 2 fully independent channels
    • 4-20 mA Input, Output Signal
    • HART® compatible
    • Line & Load short/open circuit detection
    • Field fault mirroring to the PLC AO
    • In-field programmability by DIP Switch
    • High Accuracy
    • Three port isolation, Input/Output/Supply
    • High Density, two channels per unit
    CHANNELS
    2

    Discover: D5000

    Technical data

    Technical Data

    Supply

    Voltage 24 Vdc nom (18 to 30 Vdc), reverse polarity protected
    Current Consumption 70 mA @ 24 Vdc with 20 mA output on 500 Ω load, typical.
    Power Dissipation 1.3 W @ 24 Vdc with 20 mA output on 500 Ω load, typical.

    Input

    Type 4 to 20 mA with ≤ 2.5 V voltage drop, reverse polarity protected in normal operation, ≥ 5 kΩ impedance (≈ 2 mA sinking from 10 to 30 Vdc) when fault condition detected.

    Output

    Type 4 to 20 mA, on max. 700 Ω load.
    Response time 25 ms (0 to 100 % step change).

    Fault

    Type Field device and wiring open circuit or short circuit detection; short circuit detection can be disabled via dip-switch.
    Short output load resistance < 50 Ω or < 100 Ω dip-switch selectable (≈ 2 mA forcing to detect fault).
    Open output load resistance > (21 V / Loop current) -300 Ω (for example, if Loop current = 20 mA: load resistance > (21 V / 20 mA) -300 Ω = 750 Ω).
    Fault signaling voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition).
    Open-collector/drain rating 100 mA @ 35 Vdc (≤ 1.5 V voltage drop).
    Leakage current ≤ 50 μA @ 35 Vdc.
    Response time ≤ 30 ms.

    Performance

    Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
    Calibration accuracy ≤ ± 0.1 % FSR.
    Linearity accuracy ≤ ± 0.1 % FSR.
    Temp. influence ≤ ± 0.01 % FSR on zero/span for a 1 °C change.

    Isolation

    Test Voltage I.S. Out/In 2.5 kV; I.S. Out/Supply 2.5 kV; I.S. Out/Fault 2.5 kV; I.S. Out/I.S. Out 500 V; In/Supply 500 V; In/In 500 V; Fault/In 500 V; Fault/Supply 500 V; Fault/Fault 500 V.

    Environmental conditions

    Operating temperature temperature limits –40 to +70 °C.
    Storage temperature temperature limits –45 to +80 °C.

    Safety description

    Equipment Associated apparatus and non-sparking electrical equipment.
    Safety parameters Uo = 25.9 V, Io = 93 mA, Po = 595 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.

    Mounting

    Type DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
    Weight about 145 g
    Connection by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
    Dimensions Width 12.5 mm, Depth 123 mm, Height 120 mm.

    Download

    Datasheet D5020D

    Instruction manual, 5020S-5020D

    Instruction manual, D5000 – D5200 Series

     

    G.M. International srl